Capital Hood Cleaning


Go to content

California Mechanical Code

California Code of Regulations Title 24, Part 4
California Building Standards Commission

514.3 Inspection for Grease Buildup.


514.3.1 The entire exhaust system shall be inspected for grease buildup by a properly trained, qualified, and certified company or person(s) acceptable to the Authority Having Jurisdiction in accordance with Table 5-4.
 

TABLE 5-4 EXHAUST SYSTEM INSPECTION SCHEDULE [NFPA 96: TABLE 11.4]

TYPE OR VOLUME OF COOKING FREQUENCY
FREQUENCY

Systems serving solid-fuel cooking operations
Monthly
Systems serving high-volume cooking operations such as 24-hour cooking, charbroiling, or wok cooking
Quarterly
Systems serving moderate-volume cooking operations
Semiannually
Systems serving low-volume cooking operations, such as churches, day camps, seasonal businesses, or senior centers.
Annually
Cleaning of Exhaust Systems.


514.4.1 Upon inspection, if the exhaust system is found to be contaminated with deposits from grease-laden vapors, the contaminated portions of the exhaust system shall be cleaned by a properly trained, qualified, and certified company or person(s) acceptable to the Authority Having Jurisdiction. [NFPA 96:11.6.1]

514.4.2 Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to remove combustible contaminant’s prior to surfaces becoming heavily contaminated with grease or oily sludge. [NFPA 96:11.6.2]

514.4.3 At the start of the cleaning process, electrical switches that could be activated accidentally shall be locked out. [NFPA 96:11.6.3]

514.4.4 Components of the fire suppression system shall not be rendered inoperable during the cleaning process. [NFPA 96:11.6.4]

514.4.5 Fire-extinguishing systems shall be permitted to be rendered inoperable during the cleaning process where serviced by properly trained and qualified persons. [NFPA 96:11.6.5]

514.4.6 Flammable solvents or other flammable cleaning aids shall not be used. [NFPA 96:11.6.6]

514.4.7 Cleaning chemicals shall not be applied on fusible links or other detection devices of the automatic extinguishing system. [NFPA 96:11.6.7]

514.4.8 After the exhaust system is cleaned, it shall not be coated with powder or other substance. [NFPA 96:11.6.8]

514.4.9 When cleaning procedures are completed, all access panels (doors) and cover plates shall be restored to their normal operational condition. [NFPA 96:11.6.9]

514.4.10 When an access panel is removed, a service company label or tag preprinted with the name of the company and giving the date of inspection or cleaning shall be affixed near the affected access panels. [NFPA 96:11.6.10]

514.4.11 Dampers and diffusers shall be positioned for proper airflow. [NFPA 96:11.6.11]

514.4.12 When cleaning procedures are completed, all electrical switches and system components shall be returned to an operable state. [NFPA 96:11.6.12]

514.4.13 When an exhaust cleaning service is used, a certificate showing the name of the servicing company, the name of the person performing the work, and the date of inspection or cleaning shall be maintained on the premises. [NFPA 96:11.6.13]

514.4.14 After cleaning or inspection is completed, the exhaust cleaning company and the person performing the work at the location shall provide the owner of the system with a written report that also specifies areas that were inaccessible or not cleaned. [NFPA 96:11.6.14]

514.4.15 Where required, certificates of inspection and cleaning and reports of areas not cleaned shall be submitted to the Authority Having Jurisdiction. [NFPA 96:11.6.15]
 

 

Back to content | Back to main menu